Rack-mount systems in general
The quality and layout of your racks and cabinets can save
you hours in frustration, keep your equipment organized, and reduce the
length of downtime by speeding repairs.
When comparing racks and cabinets, examine the items in person. Ask to
see some in a data center near you. Buyer beware.
Vertical columns with holes for mounting equipment
Over the years several different rack mounting scemes have come out,
varying from 16" to 49". These widths are measured horizontally from centre
of hole to center of hole.
The 2 surviving standards are the 19" and the 23". The 23" standard is
used by the telecommunications industry and virtually everyone else uses
the 19" standard.
Equipment intended for rackmount is sized vertically by "U" units, which equals 1.75
inches.
Compliant hardware is built in multiples of this 1.75" unit.
There were tape measures made that were calibrated in rack units, they are difficult to find.
Note that the holes are unevenly spaced. Narrow gap, wide gap, wide gap and back to narrow.
Your equipment should always line up at the top and bottom with narrow gaps.
Doing otherwise will leave you with a sloppy unprofessional installation.
Recently, 1-U high computer servers have become available.
Open racks vs. closed cabinets
Open rack systems are more useful for short equipment with many
wires, like hubs, switches, and routers.
Closed cabinets are more useful for deep things like servers, and when
you want to lock down physical access.
Mounting column style
Round threaded
10-32 or 10-24
Round unthreaded
Requires clip-nuts
Square punched
Square-punched is often referred to as Compaq-style.
Square-punched requires the use of clip or cage nuts and
can be inconvenient unless sliding rails are designed
specifically for that style.
When using square-hole racks, quality nuts are very
important. There are at least two styles: clip nuts have a
thin metal clip that clips over the edge of the column and are easily dislodged; cage nuts clips into the square.
Mounting methods
Front bracket only
Used for lighter equipment, such as network devices and KVMs.
Four post
Used for larger equipment.
Shelf
Great for monitors, keyboards, and oddly shaped equipment.
Sliding rail
Mounts on front and rear rails.
Sliding rails are mounted individually to the side columns and
then the computer is slid into place.
Some rail mounts will interfere with center-side columns and
the center columns must be removed.
Use sliding rails for mounting computers, whenever possible,
as it makes mounting the hardware easier and allows you to slide
the machine out for maintenance.
When using sliding rails, ALWAYS lock the computer in place with
front-mounted screws or risk catastrophic tipping.
Whenever possible, when ordering equipment, specify rail mount.
Rack Features To Look For
Always make sure shelves are available for any rack system you
buy, and buy a few extra; they come in handy.
Front-column to mid- and rear-column spacing should be adjustable
and is critical to easing the mounting of computers.
Always order deep cabinets, as many servers are quite deep, and
you will need space for routing the wires. Cabinets should be
about 32-36" deep, on the external dimension.
Some racks are connectible with a kit that removes the sides and
ties the cabinets together to make an extra wide cabinet making
it easier to run wires between sets of 19" racks.
Fit and finish count. Look for dangerous undebarred edges.
Determine if you can specify keyed-alike doors
Installation Suggestions
Whenever equipment uses the rear or mid-rails, try to keep the
same type of equipment in the same rack.
When mounting many odd-sized units in one rack, consider using
shelves instead of rail-mounts.
Always mount equipment in such a way that the side of the box
that
needs access to the cables is on the same side. This means most
hubs and switches and some routers should actually be mounted
on the rear rail. This means you don't have to pass cables from
front to back of the cabinet.
Use large-head Phillips-head screws, called truss head in
catalogs. Better yet are rack specific screws. These are truss head screws that have a unthreaded portion to help align the screw. Do not use thread-cutting screws with little teeth on
the tip of the screw, as sold by some network equipment
companies. You can cross thread these and ruin your threads.