The Design and Organization of Data Centers/Appendix A

Reference material by Wikibooks contributors. This retains its source identity and is not 411 news reporting.

Power Air conditioning Common Values Chiller calcs Assuming that all wattage consumed will end up as dissipated heat (servers do very little mechanical work or yield very little light); Wattage times 3.41 = BTU/hr Example: Server draws 10 amps at 120vac 10 amps X 120 vac = 1200 voltamps (aprox 1200 watts) 1200 VA X 3.41 = 4092 BTU/hr